Technical data
14.1 SIRIUS 3RA6 compact starter
SIRIUS 3RA6 Compact Starter
System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02
151
Order number 3RA61
3RA62
3RA691.-.A
Service life
External auxiliary switch block,
internal auxiliary switch
- Mechanical endurance
- Electrical endurance
AC-15, 230 V
DC-13, 24 V
DC-13, 110 V
DC-13, 220 V
Short circuit and overload signaling switches
- Mechanical endurance
- Electrical endurance AC15
At 6 A
At 3 A
At 1 A
At 0.3 A
At 6 A
At 3 A
At 0.5 A
At 0.2 A
At 1 A
At 0.55
At 0.3 A
At 0.1 A
At 0.04 A
At 0.3 A
At 0.1 A
At 0.05 A
At 0.018 A
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
Switching cycles
10 million
200,000
500,000
2,000,000
10,000,000
30,000
100,000
2,000,000
10,000,000
40,000
100,000
300,000
2,000,000
10,000,000
110,000
650,000
2,000,000
10,000,000
20,000
6,050 (230 V; 3 A)
Contact reliability At 17 V, 5 mA Switching cycles 1 faulty switching operation
per 100 million
Short-circuit protection
External auxiliary switch block
Fuse links gL/gG
NEOZED 5SE, DIAZED 5SB, NH 3NA
(I
K
≤ 1.1 kA)
Miniature circuit breakers up to 230 V with
C characteristic
Short-circuit current I
K
< 400 A
Internal auxiliary switch
Fuse links gL/gG
NEOZED 5SE, DIAZED 5SB, NH 3NA
(I
K
≤ 1.1 kA)
Miniature circuit breakers up to 230 V with
C characteristic
Short-circuit current I
K
< 400 A
A
A
A
A
10
10
10
10