Connecting
9.4 Connecting the compact starter (24 V) with optional AS-i mounting module
SIRIUS 3RA6 Compact Starter
System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02
77
9.4 Connecting the compact starter (24 V) with optional AS-i mounting
module
To enable communication via an AS-Interface, the AS-i mounting module must first be
installed on the compact starter (24 V). Then the AS-i mounting module can be connected to
the AS-Interface using the AS-i cables.
9.4.1 Connecting the AS-Interface
Connection method
The following cables are required:
Cables for connecting an AS-Interface
24 VDC AUX PWR cable for supplying the final controlling element
In order for the cables to be secured within the connectors, they must have a conductor
cross-section of 2 x (0.5 ... 0.75) mm
2
.
Contact
NOTICE
There is a risk of damage to the AS-i mounting module.
When working on the AS-i mounting module, please observe the ESD regulations, as
electrostatic charging can damage it.
The insulation displacement terminals make contact with the cables automatically when the
connector cover is attached.
1
$8; 3:5
$6L
2
Figure 9-3 Contact with cables

Table of Contents

Other manuals for Siemens SIRIUS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS Series and is the answer not in the manual?

Siemens SIRIUS Series Specifications

General IconGeneral
BrandSiemens
ModelSIRIUS Series
CategoryController
LanguageEnglish

Related product manuals