Installing Reflexor Operating Mode
1. From the [Meter Type] menu press the <Right Arrow>, select the desired channel setup
and press <ENT>.
2. Press the <Right Arrow>, scroll to [Reflexor] and press <ENT>.
3. At the [Channel Setup] menu press the <Right Arrow>.
4. Scroll down to
[Create/Name Site] and create a site or use a previous Saved Site setup by
highlighting [Recall Site].
Note
If a previous Saved Site is recalled, and the same sensor and location is used, then no
other installation steps are required.
5. Press the <Left Arrow> and scroll to [Pipe Data] and enter the required pipe data.
Sensor Selection
1. From [Pipe Data] scroll to the [Install Xdcr] menu and press the <Right Arrow>.
2. At [Transducer Model], press the <Right Arrow> and select the proper group of sensors
that match the mounted sensor set. For all 191N, select 190.
3. At [Transducers Size], select the proper size of sensor mounted. For all 191N, select 191.
Note
If the Flow Volume and Time units units are not set to the default units of Gallons per
Minute, then it
is recommended to change those units now by use of the [Flow/Total Units]
menu.
Functions
7.11 Reflexor
FUP1010 IP67 Portable Flowmeter
Operating Instructions, 02/2010, A5E02951522A Revision 01
101