7. While holding this sensor in place, bring the chain around the pipe and attach the closest
cross-link onto the "S" hook of the EZ clamp.
8. Tighten the adjusting
nut until the chain is just snug around the pipe. Ensure that the chain
is straight around the pipe and the sensor contacts the pipe at the white dot just under the
front label. Ensure that there is equal space on either side of the dot between the edges of
the sensor and pipe. Adjust if necessary.
9. Tighten chain and ensure that the sensor does not move while tightening. Do not over
tighten.
10.Attach the second sensor to the spacer bar at the index hole.
Note
In some cases
the sensors may have two sets of holes for securing the spacer bar. When
using the EZ Clamp assembly use the lower set of holes when attaching the spacer bar.
11.Do not apply any couplant to the second sensor. First attach the spacer bar assembly, with
the second
sensor attached to it, to the mounted sensor by inserting an index screw through
the REF hole and into the lowest hole on the sensor. Tighten the screw.
12.Visually check that the spacer bar is axially aligned with the pipe.
13.Hold spacer bar assembly in this position and draw a pencil or chalk line along the back
edge of the sensor and a dot below the sensor label white dot. See "A" below.
14.Disassemble the spacer bar and second sensor from the mounted sensor. Remove the
second sensor from the spacer bar.
Connecting
5.2 Sensor Wiring
FUP1010 IP67 Portable Flowmeter
44
Operating Instructions, 02/2010, A5E02951522A Revision 01