EasyManua.ls Logo

SolarCity H6 - Grounding Connections; Using the Spring Clamp Connectors

SolarCity H6
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
H6 Hybrid Inverter - Installation & Operation Guide
62
Copyright 2017 SolarCity Corporation. All rights reserved.
5.4 - Grounding Connections
Equipment grounding must be connected to the grounding buses within the SolarCity H6
inverter:
The SolarCity H6 Inverter operates with ungrounded PV source and output circuits in
accordance with NEC 690.35.
Size the Grounding Electrode Conductor and Equipment Grounding Conductors per 2014
NEC690.47(C)(3)
PV array grounding conductor(s).
Battery pack
Main electrical panel
Backup electrical panel
The SolarCity H6 inverter is designed and certified to meet the lightning and surge
requirements contained in UL 1741, IEEE 1547, and ANSI/ IEEE 62.41/62.42 AC.
5.5 - Using the Spring Clamp Connectors
The PV array, battery pack, communications, backup panel, and AC grid connections use
spring-clamp connectors.
Figure 5-5
displays the general process of connecting an insulated wire to a spring clamp
connector. The detailed procedure is as follows:
1. Trim at least 3/8” (10mm) off the end of the wire to remove any damaged or corroded
conductor material.
2. Strip 3/4” (20mm) of insulation off the end of the wire, being sure not to break or damage
the conductor(s).
3. Route the wire to the correct connector, as shown in
Figure 1-2
,
Figure 3-11
,
Figure 5-1
,
and in
“Inverter Wiring Box” on page 27
.
WARNING: THE SOLARCITY INPUT AND OUTPUT CONNECTIONS ARE
ELECTRICALLY ISOLATED FROM THE ENCLOSURE. THE INSTALLER IS
RESPONSIBLE FOR INCLUDING SYSTEM GROUNDING THAT COMPLIES
WITH NEC AND ANSI/NFPA 70.
SHOCK HAZARD: ENSURE THAT NO LIVE VOLTAGES ARE PRESENT ON ANY
WIRE THAT YOU ARE CONNECTING TO THE INVERTER.

Table of Contents