H6 Hybrid Inverter - Installation & Operation Guide
80
Copyright 2017 SolarCity Corporation. All rights reserved.
• ZigBee (Xbee) Module
6.2.5 - Clear Fault Menu
This menu allows you to clear arc, ground, and other faults. To clear a fault:
1. Select the Clear Fault menu.
2. Use the [UP] and [DOWN] buttons to find the type of fault to clear, and then press
[ENTER].
3. User the [UP] and [DOWN] buttons to select Yes, and then press [ENTER].
The available options are:
• Clear ARC: Clear arc fault.
• Clear Ground: Clear ground fault.
• Clear Other: Clear other faults.
6.2.6 - Soft Shutdown Menu
This menu allows you to shutdown the SolarCity H6 inverter. You may select either Yes to
proceed with the soft shutdown or No to cancel.
6.2.7 - Grid Settings Menu
This menu displays the following grid settings:
• Hi AC Volt (%): 110%
• Low AC Volt (%): 79%
• High Frequency: 61.0Hz
• Low Frequency: 58.0Hz
• Grid rec – time: 300sec
• HV time (ms): 0.2sec
• LV time (ms): 1.2sec
• HF time (ms): 0.2sec
• LF time (ms): 9.2se c
• Reactive PWR (KW): 100.00%
• CosPhi: 80.00 @ 0.80 (Range 0.8 to 1.00 [0.01] negative [Capacity])