GB.GOLDSKE.160901
www.swegon.com 103
We reserve the right to alter specifications without notice.
1)
Cannot be blocked.
2)
The delay is adjustable.
3)
Adjustable.
4)
Stops the AHU if the temperature is below the adjustable limit.
5)
Inactive as factory setting.
6)
Contact Swegon or their representative.
7)
Alarm group 38 = MIRU Control 1. Alarm group 39 = MIRU Control 2. Alarm group 40 = MIRU Control 3. Alarm group 41 = MIRU
Control 4. Alarm group 42 = MIRU Control 5. Alarm group 43 = MIRU Control 6. Alarm group 44 = MIRU Control 7. Alarm group 45
= MIRU Control 8. Alarm group 46 = MIRU Control 9. Alarm group 47 = MIRU Control 10.
8)
Alarm group 49 = Supply air fan 1A. Alarm group 50 = Supply air fan 2A. Alarm group 51 = Supply air fan 3A. Alarm group 52 =
Supply air fan 1B. Alarm group 53 = Supply air fan 2B. Alarm group 54 = Supply air fan 3B.
9)
Alarm group 55 = Extrat air fan 1A. Alarm group 56 = Extrat air fan 2A. Alarm group 57 = Extrat air fan 3A. Alarm group 58 =
Extrat air fan 1B. Alarm group 59 = Extrat air fan 2B. Alarm group 60 = Extrat air fan 3B.
Alarm No.
Alarm text
Function
Priority Stop Delay Resetting
0 = Blocked 0 = In operat. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
Alarm group 61: Supply air fan, I/O module
61:1 SUPPLY AIR FAN NO. 1A I/O MODULE COMMUNICATION
ERROR
The air handling unit's control unit cannot establish correct
communication with supply air fan no. 1A I/O module.
A 1
3)
10 s 1
61:6 SUPPLY AIR FAN NO. 2A I/O MODULE COMMUNICATION
ERROR
The air handling unit's control unit cannot establish correct
communication with supply air fan no. 2A I/O module.
A 1
3)
10 s 1
61:11 SUPPLY AIR FAN NO. 3A I/O MODULE COMMUNICATION
ERROR
The air handling unit's control unit cannot establish correct
communication with supply air fan no. 3A I/O module.
A 1
3)
10 s 1
Alarm group 62: Extract air fan, I/O module
62:1 EXTRACT AIR FAN NO. 1A I/O MODULE COMMUNICATION
ERROR
The air handling unit's control unit cannot establish correct
communication with extract air fan no. 1A I/O module.
A 1
3)
10 s 1
62:6 EXTRACT AIR FAN NO. 2A I/O MODULE COMMUNICATION
ERROR
The air handling unit's control unit cannot establish correct
communication with extract air fan no. 2A I/O module.
A 1
3)
10 s 1
62:11 EXTRACT AIR FAN NO. 3A I/O MODULE COMMUNICATION
ERROR
The air handling unit's control unit cannot establish correct
communication with extract air fan no. 3A I/O module.
A 1
3)
10 s 1