GB.GOLDSKE.160901
80 www.swegon.com
We reserve the right to alter specifications without notice.
E-mail
6.4.20.4 EIA-485
Specify protocol and settings for EIA-485.
Settings:
Value Setting range Factory setting
Protocol Inactive/Modbus/EXOline/
Metasys N2 Open/LON
Modbus
Baud rate 4800/9600/19200/38400 9600
Parity None/Even/Odd None
Stopbits 1/2 2
Modbus ID/
Metasys ID/PLA
1 - 247 1
ELA 1-255 1
Shortest
feedback delay
0 - 100 ms 0 ms
EIA-485
6.4.20.5 Modbus TCP
Specify settings for Modbus TCP.
Settings:
Value Factory setting
Port number 502
Approved client IP address 0.0.0.0
Approved client netmask 0.0.0.0
Modbus TCP
6.4.20.3 E-mail
You can select whether the AHU shall handle outgoing e-mail
here.
The settings can be entered on the AHU web page. See separate
instructions.
Settings:
Value Setting
range
Factory
setting
SMTP server External/Internal External
SMTP server Optional address
SMTP port number 25
SMTP username Optional, to be entered on
the web page
SMTP password Optional, to be entered on
the web page
Encryption On/Off Off
E-mail sender Optional, to be entered on
the web page
E-mail reply path Optional, to be entered on
the web page
6.4.20.6 BACnet IP
Enter the BACnet IP settings.
Settings:
Value Factory setting
Network number Ext. B 0
Internal network number A 0
Device ID 0
Port number 47808
BACnet IP

Table of Contents