6.4.1.6 Unit
The required unit of airflow and unit of pressure can be set.
Settings:
Value Setting range Factory
settings
Unit of airflow l/s
m
3
/s
m
3
/h
cfm
m
3
/s
Unit of pressure Pa
psi
in.wc
Pa
6.4.1.7 Air adjustment
The speed of the fans can be locked for up to 72 hours. When
the function is activated, the speed is locked at the current speed
of operation. This is practical when making airflow adjustments
in the duct system and air terminals. The desired period is preset,
but can be interrupted earlier by selecting Stop or by changing
the time setting to 0.
Unit
Air adjustment
Set point displacement
6.4.1.5 Set point displacement
The airflow is regulated between two flows in response to an
0-10 V DC input signal from an external signal, for example a po-
tentiometer. The TBIQ-3-2 IQlogic
+
module accessory is required.
Set point displacement can be used e.g. in assembly halls, where
a higher rate of air change is needed under full-load conditions.
The function is activated only when the AHU fans operate at
high speed.
On a 0-10 V DC signal, the fans are gradually accelerated from
the AHU’s high speed setting to its max. speed setting. On a
max. input 10 V DC signal, the AHU fans operate at max. speed.
The function must be activated separately for the supply air fan
and for the extract air fan.
Settings:
Value Setting
range
Factory
setting
Supply air On/Off Off
Extract air On/Off Off
6.4.1.4 Optimize
The Optimize function optimises the air handling unit's airflow
for the connected WISE system; see separate documentation for
the WISE.
The function requires that the duct pressure setting is preset
regulation type.
Settings:
Value Setting
range
Factory
setting
Optimize On/Off Off
Optimize