Regulation mode
6.4.2.3 Regulation mode
Select ERS 1, ERS 2, Supply air, Extract air, ORS or ORE regulation
Settings:
Value Setting
range
Factory
setting
Temperature
regulation mode
ERS 1/ERS 2/Supply air/
Extract air/ORS/ORE
Supply air
6.4.2.5 Set point displacement
Used for changing the supply air and extract air temperature set
points by means of an external 0-10 VDC signal. For example,
the temperature can be increased or decreased at certain times
of the day by means of an external timer or potentiometer.
The accessory, IQlogic
+
module TBIQ-3-2, is required.
The set point can be influenced by ±5 °C.
If the AHU is operating in the supply air regulation or ORS regula-
tion mode, the supply air temperature set point is displaced and
the AHU is operating in the extract air regulation or ORE regula-
tion mode, the extract air temperature set point is displaced.
When the AHU is operating in the ERS regulation 1 mode, the
difference between extract air and supply air is influenced. The
difference cannot be less than 0 °C. The difference will decrease
as the input signal increases.
If the AHU is operating in the ERS regulation 2 mode, the supply
air set point will be displaced.
When the function is activated, the set point is displaced as plot-
ted in the diagram to the right.
Set point displacement will not affect any possible extra tem-
perature zone (Xzone) which regulates according to its ordinary
set point if set point displacement is in operation.
Settings:
Value Setting
range
Factory
setting
Set point displacement On/Off Off
1050
+5
+4
+3
+2
+1
0
-1
-2
-3
-4
-5
Control signal V DC
Set point displacement involves the following:
Control signal 0 V DC: The set point is decreased by 5 °C.
Control signal 5 V DC: No change in set point.
Control signal 10 V DC: The set point increases by 5 °C.
Set point displacement
Set point displacement °C
Unit of temperature
6.4.2.4 Unit of temperature
The desired unit of temperature can be set.
Settings:
Value Setting range Factory
settings
Unit °C/ °F °C