Function Factory-preset value Adjusted value
External temperature sensors
Room sensor mode
X
Medium
Min. Max. Medium Min. Max.
Room temp from communication
On
X
Off
On Off
Room temp., for intermittent night heat only
On
X
Off
On Off
Room temp., for summer night cooling only
On
X
Off
On Off
Outdoor air sensor 1
On
X
Off
On Off
Outdoor air sensor 2
On
X
Off
On Off
Outdoor air sensor 3
On
X
Off
On Off
Outdoor air sensor 4
On
X
Off
On Off
Outdoor air sensor mode
X
Medium
Min. Max. Medium Min. Max.
Outdoor temp from communication
On
X
Off
On Off
Xzone room sensor 1
On
X
Off
On Off
Xzone Room sensor 2
On
X
Off
On Off
Xzone Room sensor 3
On
X
Off
On Off
Xzone room sensor 4
On
X
Off
On Off
Xzone, Room sensor function
X
Medium
Min. Max. Medium Min. Max.
Xzone, Room temp. from communication
On
X
Off
On Off
Regulation sequence
Heat mode 1
Cool mode 1
Min. exhaust air
Min. exhaust air
On
X
Off
On Off
Min. exhaust air temperature °C 5.0
Morning Boost
Morning Boost
On
X
Off
On Off
Start time hh:mm. 00:00
Supply air, set point 50% of max. supply air for AHU alt. 100
Pa
Heating boost
Heating boost
On
X
Off
On Off
Start limit K 3
Cooling boost
Cooling boost
X
Inactive
Comfort Economy Inactive Comfort Economy
Sequence Comfort and economy
Sequence Comfort and economy
Economy and sequence Economy and sequence
Sequence and comfort Sequence and comfort
Comfort, economy and sequence Comfort, economy and sequence
Start limit (Comfort) K 3
Intermittent night heat
Intermittent night heat
On
X
Off
On Off
Air recirculation
X
On
Off On Off
Room temperature, start °C 16
Room temperature, stop °C 18
Supply air temperature, set point °C 28
Supply airflow, set point 50% of max. supply air for AHU alt. 100
Pa
Extract air flow, set point 50% of max. supply air for AHU alt. 100
Pa
Summer night cool
Summer night cool
On
X
Off
On Off
Start time hh:mm 23:00
Stop time hh:mm 06:00
Outdoor air start °C 10
Extract air start °C 22
Extract air stop °C 16
Supply air, set point °C 10
Down regulation (airflow/pressure)
Down regulation
Inactive
X
Supply air
Inactive Supply air
Supply and extract air Supply and extract air