GB.GOLDSKE.160901
58 www.swegon.com
We reserve the right to alter specifi cations without notice.
Settings
6.4.10 Air handling unit
6.4.10.1 Settings
Set the type of air handling unit here. The type of air
handling unit is normally preset for the unit supplied;
except the GOLD SD extract air unit which must be set
here.
N.B.! Do not change the air handling unit setting to a
type that differs from the one supplied. If you do so, the
air handling unit will not operate satisfactorily.
The air handling unit can be given a specifi c name (e.g. the
unit's serial number). Naming in the hand-held terminal can
only be done with digits, however on the web page the naming
can also be done with alphabetical characters. The given name
is then shown in all the images in the hand-held terminal and
web page.
The type of AHU, size of the supply air and extract air fan re-
spectively can be viewed.
GOLD RX/PX/CX
The AHU’s fan position 1 (left-hand fan seen from the inspection
side, see illustrations) can be read and preset.
N.B.! This changes the function of the fans from supply
air to extract air and vice versa. GOLD RX size 04-120/
GOLD RX Top can be changed at the site. The other vari-
ants must not be changed from the factory setting.
The fan position in the fl ow chart can be read and should be set
according to the AHU's actual confi guration.
GOLD SD
The fan position, upper or lower level, can be read and should be
set according to the AHU’s actual confi guration.
Settings:
Value Setting
range
Factory
setting
Type of air handling unit GOLD RX/GOLD
PX/GOLD CX/
GOLD SD Sup-
ply air/GOLD
SD Extract air/
GOLD SD Sup-
ply air+CX/
GOLD SD Supply
air+Extract air/
GOLD SD Sup-
ply air+Extract
air+CX
Type of air
handling
unit sup-
plied, except
the GOLD
SD extract
air handling
unit
GOLD RX/PX/CX
Name Optional
Fan position 1 Extract air/
Supply air
Extract air
Flow chart, supply air fan
position
Upper level/
Lower level
Lower level
GOLD SD
Name Optional
Flowchart fan position Upper level/
Lower level
Lower level
Air handling
unit
GOLD RX 04-40
GOLD RX Top
Fan pos. 1 set as supply air
(left-hand inspection side)
Fan pos. 1 set as extract air
(right-hand inspection side)
Outdoor air Supply air Extract air Exhaust air
Fan arrangement 1
Fan arrangement 2
Fan pos. 1 set as extract air
(right-hand inspection side)
Fan pos. 1 set as supply air
(left-hand inspection side)
Fan pos. 1 set as extract air
(right-hand inspection side)
Fan pos. 1 set as supply air
(left-hand inspection side)