Heat
6.4.11 Heat
6.4.11.1 Status
All the relevant values can be read here. Used for performance
checks.
6.4.11.2 Pre-heat
By preheating the outdoor air, it is possible to prevent moisture
precipitation in the AHU's outdoor air fi lter, to reduce the risk of
frosting in the heat exchanger and to eliminate the risk that pres-
sure sensors and motor control systems are operating in too low
ambient temperature.
See also the Pre-heat function guide for more detailed informa-
tion.
Settings:
Value Setting
range
Factory
setting
Pre-heat On/Off Off
Pre-heat set point -40 – +40°C 5°C
Periodic operation of pump On/Off On
Periodic operation of valve On/Off On
Periodic operation interval 0-168 hrs. 24 hrs.
Periodic operation period 0-60 min. 3 min.
Alarm input, function Inactive/Alarm
on open contact/
Alarm on closed
contact/Contactor
function
Inactive
Status
Pre-heat