6.4.21 Base setting
Used for saving, loading and restoring the settings.
Date and time for the latest saved backup copy can be viewed.
The AHU's settings/communication settings are saved/loaded to/
from the control unit's internal memory or external SD circuit
card that can be inserted into the control unit.
The AHU settings involve all settings except communication set-
tings.
Communication settings involve all settings (except AHU set-
tings).
Factory reset and Reset air handling settings, means restoring
all the settings except communication settings and calibrated
values.
Factory reset and Reset air handling and communication settings,
means restoring all the settings except calibrated values.
Total Factory reset means restoring all the settings. Note
that even the calibrated values on the pressure sensor,
etc., will be restored.
Settings:
Value Alternative
Air handling settings
Export air handling settings Export to local backup/Export to
SD card
Import air handling settings Import from local backup/Import
from SD card
Communication
settings
Export communication
settings
Export to local backup/Export to
SD card
Import communication
settings
Import from local backup/Import
from SD card
Factory reset Reset air handling settings/Reset
air handling and communication
settings/Total Factory reset
Base setting
IQnavigator user
6.4.22. Users
The requirements for password can be activated here under User
level (local). The password is always 0000.
Settings:
Value Setting
range
Factory
setting
Requirements for user password On/Off Off
Users