GB.GOLDSKE.160901
52 www.swegon.com
We reserve the right to alter specifications without notice.
Calendar 1
6.4.3.5 Calendar 1 and 2
The specific days when Exceptions schedule 1 or 2 shall
apply can be set in Calendars 1 and 2. On condition that
Calendar 1 or 2 is selected, see previous section. In other
cases, these settings will have no effect.
There is a total of ten possible settings under each calen-
dar and various functions can be selected for each.
Settings (For Calendar 1 and Calendar 2 respectively):
Value Setting
range
Factory
setting
Function 1-10 Inactive/Date/Date range/
Weekday
Inactive
Date
Start date Year/Month/Day
Start weekday Each day/Monday/Tuesday/
Wednesday/Thursday/Friday/
Saturday/Sunday
Each day
Date range
Start date Year/Month/Day
Stop date Year/Month/Day
Weekday
Start date Month 1-12/Odd/Even/Each
Day 1-7/8-14/15-21/22-28/29-
31/Latest 7 days/Each day
Start weekday Each day/Monday/Tuesday/
Wednesday/Thursday/Friday/
Saturday/Sunday
Each day
6.4.3.6 Prolonged operation
The control unit inputs for external low speed (terminals 14-15)
and external high speed (terminals 16-17) respectively, can be
supplemented with Prolonged operation. They can be used for
overtime running activated by a pushbutton, for example.
The required time in hours and minutes can be set as follows.
Settings:
Value Setting
range
Factory
setting
Ext. low speedt 0:00 - 23:59 00:00
Ext. high speed 0:00 - 23:59
(hrs.:min.)
00:00
(hrs.:min.)
Calendar 2
Prolonged operation

Table of Contents