6.4.24 Manual test
NB! Manual test running can cause indoor comfort prob-
lems. There is also risk of overloading the system. The
responsibility for discomfort and overload rests totally on
the person who activates the function.
When you enter manual test, you must select a safe mode or
live mode. Safe mode involves stopping the AHU and being able
to run each installed function separately or together. In the safe
mode the heat exchanger is oversteered in relation to the fan
speed. Live mode involves permitting the AHU to continue to
operate in the normal operating mode and installed functions
can be infl uenced manually. In this live mode the heat exchanger
is not oversteered in relation to the fan speed.
Manual test operation can take place for testing the inputs and
outputs, fans and heat exchanger, etc.
Used for installation or troubleshooting to test that wired con-
nections and functions operate correctly.
Certain alarms, functions and normal control modes will be
blocked while manual testing is in progress.
On a return to the other image groups, the controller resumes
normal operation and all settings for manual testing will be
terminated.
Each image indicates which functions can be test run.
Manual test
Notes
6.4.23 Notes
Notes can be read here. Notes can only be written on the AHU's
web page.