6.4.2.15 Down regulation (airflow/pressure)
Down regulation of the supply air flow is the last step in the
regulation sequence for heating. The supply air fan or both the
supply air and extract air fan can be selected. The extract air fan
only cannot be selected.
See also Section 6.4.2.7.
Down regulation can take place to max. of 50% of the preset
value, however not lower than the min. flow or 20 Pa.
Settings:
Value Setting
range
Factory
setting
Down regulation Inactive/Supply
air/Supply air and
extract air
Supply air
Down regulation