Alarm settings
Function Factory-preset value Adjusted value
Alarm priorities
Fire alarms
Internal fi re alarm
On
X
Off
On Off
Inernal fi re alarm reset
X
Manual
Auto Manual Auto
Internal fi re alarm after cool
Active
X
Inactive
Active Inactive
External fi re alarm 1 reset
X
Manual
Auto Manual Auto
External fi re alarm 1 after cool
Active
X
Inactive
Active Inactive
External fi re alarm 2 reset X
Manual
Auto Manual Auto
External fi re alarm 2 after cool
Active
X
Inactive
Active Inactive
Fan operation on an internal fi re
alarm
X
Inactive
Supply air Inactive Supply air
Extract air Supply and extract air Extract air Supply and extract air
Supply air fan on an int. fi re alarm % 100
Extract air fan on an int. fi re alarm % 100
Fan operation on external fi re alarm 1
X
Inactive
Supply air Inactive Supply air
Extract air
Supply and extract air Extract air Supply and extract air
Supply air fan on external fi re alarm 1 % 100
Extract air fan on external fi re alarm 1 % 100
Fan operation on external fi re alarm 2
X
Inactive
Supply air Inactive Supply air
Extract air Supply and extract air Extract air Supply and extract air
Supply air fan on external fi re alarm 2 % 100
Extract air fan on external fi re alarm 2 % 100
Order of priority
X
Ext. fi re alarm 1
Ext. fi re alarm 2 Ext. fi re alarm 1 Ext. fi re alarm 2
Int. fi re alarm Automatic Int. fi re alarm Automatic
External alarms
External alarm 1 reset
Manual
X
Auto
Manual Auto
External alarm 1 after cool
Active
X
Inactive
Active Inactive
External alarm 1 input X
Closed circuit
Open circuit Closed circuit Open circuit
External alarm 1 delay time s 10
External alarm 2 reset
Manual
X
Auto
Manual Auto
External alarm 2 after cool
Active
X
Inactive
Active Inactive
External alarm 2 input X
Closed circuit
Open circuit Closed circuit Open circuit
External alarm 2, time delay s 10
Temperature protection
Temperature protection
On
X
Off
On Off
Alarm delay s 30
Alarm limit °C 7
Temperature alarm limits
Pre-heat below set point K 5.0
Supply air below set point K 5.0
Supply air above set point K 7.0
Extract air below alarm limit °C 12.0
Outdoor temperature limit stop °C 5.0
Service period
Service period Mon. 12
Alarm priority
See alarm list