097-72020-01 Revision K – December 2005 TimeSource User’s Guide 127
Chapter 4 TL1 Reference
Commands
Initialize System
This command resets the specified processor.
The command format is:
INIT-SYS:[<tid>]:<aid>:<ctag>::1;
Response Format:
<sid> <date> <time>
M <ctag> COMPLD
/*LINK:<link>,CMD:<command>*/
;
Caution: Using this command with an <aid> of TS3100 will cause a
loss of outputs for approximately 20 minutes if ALMOUT is
SQUELCH, or unstable outputs if ALMOUT is not SQUELCH.
Aid Item Addressed
TS3100 System software
GPS GPS receiver software