Chapter 4 TL1 Reference
Commands
130 TimeSource User’s Guide 097-72020-01 Revision K – December 2005
Retrieve Alarm Equipment
This command displays current alarms for the specified equipment. The command
format is:
RTRV-ALM-EQPT:[<tid>]:<aid>:<ctag>;
If there are no alarms:
<sid> <date> <time>
M <ctag> COMPLD
/*LINK:<link>,CMD:<command>*/
;
If there is at least one alarm:
<sid> <date> <time>
M <ctag> COMPLD
"<aid>:<ntfcncde>,<condtype>,<srveff>,
<ocrdat>,<ocrtm>,,:\"<conddescr>\""..
/ *LINK:<link>,CMD:<command>*/
;
Refer to Chapter 5, Troubleshooting, for a list of all <conddescr> messages, and the
recommended action.
Aid Value Item Addressed
TS3100 – System (all TS3100 alarms)
SPAN-x x = A E1 span A input
x = B E1 span B input
RO-x x = A Remote oscillator A input
x = B Remote oscillator B input
GPS – GPS receiver