097-72020-01 Revision K – December 2005 TimeSource 3100 User’s Guide 91
Chapter 3 Installing the TimeSource 3100
Factory Default Values
TS3100 GPS ALARM TIME=3-0
SEV1=EV
SEV2=MN
SAFF1=NSA
SAFF2=NSA
GPS ANTCBLDLY=0
ANTELEVMASK=10
RO-A, RO-B ENSEMBLER=INH
MONITOR=INH
SPAN-A, SPAN-B ENSEMBLER=INH
MONITOR=INHSSM=INH
SSM=INH
SIGNAL=DIGITAL
SSMCHANNEL=4
SPAN-A, SPAN-B
LOS ALARM
TIME=24-0
SEV1=EV
SEV2=MN
SAFF1=NSA
SAFF2=NSA
SPAN-A, SPAN-B
AIS ALARM
TIME=24-0
SEV1=EV
SEV2=MN
SAFF1=NSA
SAFF2=NSA
SPAN-A, SPAN-B
LOS ALARM
TIME=24-0
SEV1=EV
SEV2=MN
SAFF1=NSA
SAFF2=NSA
SPAN-A, SPAN-B
ERROR ALARM
TIME=24-0
SEV1=EV
SEV2=MN
SAFF1=NSA
SAFF2=NSA
RO-A, RO-B LOS
ALARM
TIME=24-0
SEV1=EV
SEV2=MN
SAFF1=NSA
SAFF2=NSA
Table 3-9. Parameter Factory Settings (Continued)