11
V01.0| 2017/04
TBPN-L1-FDIO1-2IOL - Standard IO-Link
2.5.2 Process Input Data – IO-Link Master Channels
Word Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit
9
Bit
8
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
Basic
n + +1 DXP15
C7P2
DI14
C7P4
DXP13
C6P2
DI12
C6P4
--
n + 2 - DVS14 - DVS12 -
...
IO-Link chan-
nels
n + 11
…
n + 26
IOL1 – process input data (connector C6)
Structure depends on the channel parameterization
n + 27
…
n + 42
IOL2 – process input data (connector C7)
Structure depends on the channel parameterization
Diagnostics
Overcurrernt sensor supply (IOL1)
n + 43 - VERRV1
K1213
-
Overcurrent output
n + 44 SCO15 - SCO13 -
IO-Link port diagnostics
IOL1 (connector C6)
n + 45 GENR OVL VHIGH VLOW ULVE LLVU OTMP PRM
ER
EVT2 EVT1 PD
INV
HW
ER
DS
ER
CFG
ER
PPE -
IOL2 (connector C7)
n + 46 Assignment similar to port IOL1
IO-Link
Events
n + 47 Port (1st Event) Qualifier (1st Event)
n + 48 Event Code (1st Event)
…
n + 77 Port 16th Event) Qualifier (16th Event)
n + 78 Event Code (16th Event)
Name Value Meaning
DXPx
CxPy
0 Input active
1 Input active
DVSx Input value valid (Data Valid Signal)
0 The IO-Link data are valid.
Possible causes:
– Sensor supply is below the admissible range,
– IO-Link port is parameterized as simple digital input,
– No device connected to the masters,
– No input data received from the connected device (only valid for devices with an
input data length > 0),
– No reaction from the connected device to the sending of output data (only valid
for devices with an output data length >
0),
– The connected device sends an error "process input data invalid.
1 The IO-Link data are valid.