Product description
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
24
Storing a Configuration in Operation
Prerequisites
The device is connected to the Turck Safety Configurator
The memory chip is plugged from the device start and contains the actual configuration (identi-
cal configuration as in the Turck Safety Configurator).
Procedure
Load a new or changed configuration into the device via Turck Safety Configurator.
The device checks the configuration.
After the configuration validation, the configuration is copied to the memory chip.
3.8.2 Loading a Configuration from the Memory Chip
Prerequisites
Memory chip with valid configuration
Procedure
Set the rotary coding switches to 900 (F_Reset)
Execute a power cycle at the device
The device is reset
Set the rotary coding switch to an address unequal to "9xx"
Plug the memory chip containing a valid configuration onto the device
Switch-on the power supply
The configuration will be loaded from the memory chip to the device during device start.
3.8.3 Reset the Device to Factory Settings (incl. Deleting the Memory Chip)
Deleting the Configuration via Rotary Switch Setting (900)
Plug the memory chip into device
Set the rotary coding switches to 900 (F_Reset)
Execute a power cycle at the device
The device as well as the plugged memory chip are reset, the configuration is deleted.
The procedure completed as soon as the ERR LED stops blinking.