17
2018/02
TBIP-L…-FDIO1-2IOL- Safe I/O channels
Max. cable lengths
Ethernet 100 m (per segment)
Sensor/actuator 30 m
Housing
Material Fibre-glass reinforced Polyamide (PA6-GF30)
Size 60.4 × 230.4 × 24 mm (w × l ×h)
Window material Lexan
Screw material 303 Stainless Steel
Halogen-free yes
Mounting
Mounting 2 mounting holes, ? 6.3 mm
Mounting distance
Device to device
50 mm
Valid for operation in ambient temperatures mentioned
below with sufficient ventilation.
At low simultaneity factors and low ambient tempera-
tures, mounting distances of < 50 mm may be possible.
max. torque 1.5 Nm
Tests/ environmental conditions
Vibration test according to EN 60068-2-6/ IEC 68-2-47,
acceleration up to 20 g
Drop and topple according to IEC 60068-2-31/IEC 60068-2-32 1
Shock test according to EN 60068-2-27
EMC according to EN 61131-2
Protection class IP65/IP67/IP69K
Temperature range
Operating temperature - 40 °C … +70 °C (- 40 °F … +158 °F)
Storage temperature - 40 °C … +70 °C (- 40 °F … +158 °F)