Connecting to the Host
4–10 iSTAR eX Installation and Configuration Guide
status change to the C•CURE 800 host. If the external power supply battery is
low, the PMB instructs the GCM to report the status change to the C•CURE
800 host.
.
If you do not configure the Tamper, Low Battery, and AC Power Fail
inputs in the software—in the Special Purpose Inputs box shown in
Figure 4.6, they are not reported.
If the PMB is not connected or if it fails, the Low Battery and AC Power
Fail inputs are reported as true. To prevent incorrect reporting of the
inputs, clear the configuration check boxes.