Watlow F4T Controller 38 Chapter 2 Configuration Using Composer
Ramp Rate
Set the speed at which the loops set point is increased or decreased to the steps Set Point
value.
Set Point
Set the value to which the loops set point is changed by the step.
Guaranteed Soak Enable
Set On to prevent step time from elapsing whenever the loops process value differs from its
Set Point by more than Guaranteed Soak Value for the loop.
Options: On, Off
Event Input 1 to Event Input 4
Set the condition on each input for a Wait for Process or Event step.
Options:
None: do not wait for this input.
On: wait until a digital input is on or true.
Off: wait until a digital input is off or false.
Greater Than: wait until the process value is greater than the setting of the corre-
sponding Input Value parameter.
Less Than: wait until the process value is less than the setting of the corresponding In-
put Value parameter.
Input 1 Value to Input 4 Value
Set the process value against which the corresponding analog input condition is evaluated in a
Wait for Process or Event step.
Jump To Step
Set the step at which the profile should begin to repeat steps.
Number of Times
Set the how many times the Jump Loop step repeats the previous profile steps.
Note:
Number of Times is the number of times the steps are repeated not including the time
they are executed prior to reaching the Jump step. For example if step 5 of a six step
profile is a Jump with Jump To Step set to 2 and Number of Times set to 1, when the pro-
file is run starting at step 1 it executes steps as follows: 1, 2, 3, 4, 5, 2, 3, 4, 5, 6.
Event Outputs: Event Output 1 to 8 to Event Output 4
Set the state to which the profile sets each event output at the start of the step.
Options:
On: the step sets the event output on or true.
Off: the step sets the event output off or false.
Unchanged: the step does not set the event output; it remains in whatever state was
previously set.

Table of Contents

Other manuals for Watlow F4T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watlow F4T and is the answer not in the manual?

Watlow F4T Specifications

General IconGeneral
InputsThermocouple, RTD, mA, V
OutputsRelay, SSR, mA, V
CommunicationEthernet, Modbus RTU
Data LoggingYes
CertificationsCE, UL, cUL, RoHS
Control ModesPID, On/Off
Power Supply100 to 240 VAC
Operating Temperature0 to 50°C
Enclosure RatingIP65
Display4.3 in. (109 mm) color touch panel LCD
Control LoopsUp to 4