CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
During the JOG + or JOG- commands the values of P122 or P123 are
respectivelyaddedto,orsubtractedfrom thespeedreferencetogenerate
the total reference. Refer to figure 6.26.
These parameters (P124 to P131) are shown only when P221 = 8 and/
or P222 = 8 (Multispeed).
Multispeed is used when the selection of a number (up to 8) of pre-
programmed speeds is desired.
If you want to use only2 or 4 speeds, any input combination of DI4, DI5
and DI6 can be used. The input(s) programmed for other function(s)
must be considered as 0 V in the table 6.5.
It allows control of the speed by relating the values programmed in
parameters P124to P131 to a logical combination of the Digital Inputs.
The advantages of this function are stability of the fixed references and
electrical noise immunity (isolated digital inputs DIx).
Multispeed function is active when
Mode) is set to 8 (Multispeed).