CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Deceleration with ramp holding
DC Link Voltage (Ud) (P004)
With this function you can achieve an optimized deceleration time
(minimum) for the driven load.
This function is useful in application where loads with medium moment
of inertia are driven, that require short deceleration ramps.
Ifeven sotheinverterisdisabledduringtheaccelerationduetoovervoltage
(E01), reduce the value of P151 gradually, or increase the deceleration
ramp time (P101 and/or P103).
In case the supply line is permanently under overvoltage (Ud > P151),
the inverter cannot decelerate. In this case reduce the line voltage or
Ifeven afterthesesettingsthemotorcannot decelerate within therequired
deceleration time, use the dynamic braking. (For more details about the
dynamic braking, refer to item 8.10).
Type of DC Link Voltage Regulation when P152 > 0.00 and P151
are set different that than the maximum value:
Voltage reaches the regulation level during the deceleration, the
deceleration ramp time is increased and the motor is also accelerated
until the DC Link voltage leaves the defined over-voltage level. There
after deceleration is continued. Refer to figure 6.13.
Recommended values for DC Link voltage regulation level