440
ID
Function
Note
SD120
HSC0 error info
SD121
HSC2 error info
SD122
HSC4 error info
SD123
HSC6 error info
SD124
HSC8 error info
SD125
HSC10 error info
SD126
HSC12 error info
SD127
HSC14 error info
SD128
HSC16 error info
SD129
HSC18 error info
ID
Function
Note
Serial
port 0
SD140
Modbus read write
instruction execution
result
0: correct
100: receive error
101: receive overtime
180: CRC error
181: LRC error
182: station error
183: send buffer overflow
400: function code error
401: address error
402: length error
403: data error
404: slave station busy
405: memory error(eraseFLASH)
SD141
X-Net communication
result
0: correct
1: communication overtime
2: memory error
3: receive CRC error
SD142
Free format
communication send
result
0: correct
410: free format send buffer
overflow
SD143
Free format
communication receive
result
0: correct
410: send data length overflow
411: receive data short
412: receive data long
413: receive error
414: receive overtime
415: no start character
416: no end character
SD108
Current segment (No. n segment)
HSC16
SD109
Current segment (No. n segment)
HSC18
High speed counter error(SD120-SD129)
communication(SD140~SD199)
tudonghoatoancau.com