The time value is stored in register TD. The working mode of timer T0~T575 and HT0~HT95
are 16-bits linear increasing. The time range is from 0 to 32767. When the time value in TD
reaches 32767, the timer will stop timing and keep the status.
MOV T0 D0
X0
MOV TD0 D0
X0
The two instructions are the same. In the first instruction, T0 is seemed to TD0.
X0
Y0
X0
X0
Y0 T2
T2
TMR T2 K200 K10
Y0
X0 is ON, output Y0. X0 changes from ON to OFF, delay 2s then cut off Y0.
X0
T1
T2
X0
Y0
T1 T2 T1
Y0
TMR T1 K20 K10
TMR T2 K10 K10
X0 is ON, Y0 begin to twinkle. T1 is Y0-OFF time; T2 is Y0-ON time.
Note: The range of soft components mentioned above is the valid range of PLC in the X-NET
communication mode. In the MODBUS communication mode, some relays can not read and
write. The specific usable range is shown in chapter 6-2-3.