58
to 1, 000/(20+20)=25Hz input pulse can’t be processed. But, this condition could be improved
when use PLC’s special function and applied instructions (such as high speed count, input
interruption, input filter adjustment).
Dual output(Dual coils)action
X0
OUT Y0
Y0
OUT Y1
X1
OUT Y0
X0=ON X1=OFF
Y0=OFF Y1=ON
When executing dual output (use dual coil), the after one is act in priority.
As shown in the left map, please
consider the case of using the same coil
Y0 at many positions:
E.g.X0=ON, X1=OFF
The first Y0: X0 is ON, its image area is
ON, output Y1 is also ON.
The second Y0: as input X1 is OFF, the
image area is OFF.
So, the actual output is: Y0=OFF,
Y1= ON.
tudonghoatoancau.com