Standards Compliance
5
5.3 UL Standards
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 287
Model
Recomm. Gauge (AWG, kcmil)
Crimp Terminal
Model
*1
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
-, +1 +3
4038 - - - - 6
P6-14R-E
S6-14R-E
4044, 4060 - - - - 6
P6-14R-E
S6-14R-E
4075 - - - - 6
P6-14R-E
S6-14R-E
4089, 4103 - - - - 4
P4-14R-E
S4-14R-E
4140, 4168 - - - - 4
P4-56R-E
S4-56R-E
4208
- - - - 4
P4-38R-E
S4-38R-E
1/0 × 2P 1/0 × 2P - 1/0 × 2P - S1/0-38R-X
- - 3/0 × 2P - - S3/0-38R-5
4250
- - - - 2
P2-38R-X
S2-38R-X
- - - 1/0 × 2P - S1/0-38R-X
2/0 × 2P 2/0 × 2P -
- -
S2/0-38R-X
- - 3/0 × 2P S3/0-38R-5
4302
- - - - 2
P2-38R-X
S2-38R-X
- - - 1/0 × 2P - S1/0-38R-X
3/0 × 2P 3/0 × 2P - - - S3/0-38R-5
- - 4/0 × 2P - - S4/0-38R-5
4371
- - - - 1 S2-12R-X
- - - 3/0 × 2P - S3/0-12R-5
250 × 2P 250 × 2P - - - S250-12R-5
- - 350 × 2P - -
LCA350-12-X
LCAX350-12-6
4414
- - - - 1 S2-12R-X
- - - 4/0 × 2P - S4/0-12R-5
300 × 2P 300 × 2P - - -
LCA300-12-X
LCAX300-12-6
- - 400 × 2P - - LCA400-12-6
4477
- - - - 1/0 S1/0-12R-X
- - - 3/0 × 4P - S3/0-12R-5
- 4/0 × 4P 4/0 × 4P - - S4/0-12R-5
250 × 4P - - - - S250-12R-5
4568
- - -
- 2/0 S2/0-12R-X
3/0 × 4P - S3/0-12R-5
- 4/0 × 4P - - - S4/0-12R-5
250 × 4P
-
-
- -
S250-12R-5
- 300 × 4P
LCA300-12-X
LCAX300-12-6