5.3 UL Standards
286 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Table 5.17 Closed-Loop Crimp Terminals for Three-Phase 200 V Class Drives (Manufacturer: PANDUIT Corp.)
Model
Recomm. Gauge (AWG, kcmil)
Crimp Terminal
Model
*1
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
-, +1 +3
2004 - 2021 - - - - 10 P10-8R-L
2030, 2042 - - - - 8
P8-10R-Q
S8-10R-Q
2056 - - - - 6
P6-14R-E
S6-10R-E
2070 - 2110 - - - - 6
P6-14R-E
S6-10R-E
2138 - - - - 4
P4-14R-E
S4-56R-E
2169, 2211 - - - - 4
P4-56R-E
S4-56R-E
2257
- - - - 3 S2-38R-X
- - - 1/0 × 2P - S1/0-38R-X
2/0 × 2P 2/0 × 2P - - - S2/0-38R-X
- - 4/0 × 2P - - S4/0-38R-5
2313
- - - - 2 S2-38R-X
- - - 1/0 × 2P - S1/0-38R-X
- 3/0 × 2P - - - S3/0-38R-5
4/0 × 2P - - - - S4/0-38R-5
- - 250 × 2P - - S250-38R-5
2360
- - - - 1 S2-12R-X
- - - 3/0 × 2P - S3/0-12R-5
250 × 2P 250 × 2P - - - S250-12R-5
- - 350 × 2P - -
LCA350-12-X
LCAX350-12-6
2415
- - - - 1 S2-12R-X
- - - 3/0 × 2P - S3/0-12R-5
250 × 2P -
- - -
S250-12R-5
- 300 × 2P
LCA300-12-X
LCAX300-12-6
- - 350 × 2P - -
LCA350-12-X
LCAX350-12-6
*1 For use with PANDUIT Corp. heat-shrinkable tubing HSTT-series or an equivalent UL-recognized heat-shrinkable tubing rated 600 V
minimum.
Table 5.18 Closed-Loop Crimp Terminals for Three-Phase 400 V Class Drives (Manufacturer: PANDUIT Corp.)
Model
Recomm. Gauge (AWG, kcmil)
Crimp Terminal
Model
*1
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
-, +1 +3
4002, 4004 - - - - 12 P10-8R-L
4005 - 4012 - - - - 10 P10-8R-L
4018, 4023 - - - - 10 P10-10R-L
4031 - - - - 8
P8-14R-Q
S8-14R-Q