Standards Compliance
5
5.3 UL Standards
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 285
Model Terminal
Recomm. Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
(mm
2
)
Wire
Stripping
Length
*1
mm
Terminal Screw
Size and Shape
Tightening Torque
N∙m (lbf∙in)
T477
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
2/0 × 2P (× 2)
2/0 - 300
(70 - 150)
- M12
35
(310)
U/T1, V/T2, W/T3 4/0 × 4P
2/0 - 300
(70 - 150)
- M12
35
(310)
-, +3 3/0 × 4P
2 - 250
(35 - 120)
- M12
35
(310)
1/0
1/0 - 300
(50 - 150)
- M12
32 - 40
(283 - 354)
T568
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
3/0 × 2P (× 2)
2/0 - 300
(70 - 150)
- M12
35
(310)
U/T1, V/T2, W/T3 4/0 × 4P
3/0 - 300
(95 - 150)
- M12
35
(310)
-, +3 3/0 × 4P
2 - 250
(35 - 120)
- M12
35
(310)
2/0
2/0 - 300
(70 - 150)
- M12
32 - 40
(283 - 354)
T605
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
4/0 × 2P (× 2)
3/0 - 300
(95 - 150)
- M12
35
(310)
U/T1, V/T2, W/T3 300 × 4P
250 - 300
(120 - 150)
- M12
35
(310)
-, +3 4/0 × 4P
2 - 250
(35 - 120)
- M12
35
(310)
2/0
2/0 - 300
(70 - 150)
- M12
32 - 40
(283 - 354)
T720
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
250 × 2P (× 2)
3/0 - 300
(95 - 150)
- M12
35
(310)
U/T1, V/T2, W/T3 300 × 4P
250 - 300
(120 - 150)
- M12
35
(310)
-, +3 4/0 × 4P
2 - 250
(35 - 120)
- M12
35
(310)
2/0
2/0 - 300
(70 - 150)
- M12
32 - 40
(283 - 354)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
■ Closed-Loop Crimp Terminals
To comply with UL standards on drive models 2257 to 2415, 4208 to 4720, and T208 to T720, use UL-approved
closed-loop crimp terminals. Use the tools recommend by the terminal manufacturer to crimp the closed-loop crimp
terminal. Yaskawa recommends closed-loop crimp terminals and heat-shrinkable tubing from PANDUIT Corp.
Make sure that you comply with local standards for correct wire gauges in the region where you will use the drive.
Contact Yaskawa or your nearest sales representative to order.
Refer to Table 5.17, Table 5.18, and Table 5.19 to select crimp terminals as specified by drive model and wire gauge.
Note:
To comply with UL standards, use only insulated crimp terminals or crimp terminals with insulation tubing. Use UL-Listed, vinyl-coated
insulated copper wires for operation with a continuous maximum permitted temperature of 75 °C at 600 V.