Standards Compliance
5
5.3 UL Standards
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 289
Model
Recomm. Gauge (AWG, kcmil)
Crimp Terminal
Model
*1
R/L1, R1/L11
S/L2, S1/L21
T/L3, T1/L31
U/T1
V/T2
W/T3
- +3
T568
3/0 × 2 × 2 - 3/0 × 4P 3/0 × 4P - S3/0-12R-5
- 4/0 × 4P - - - S4/0-12R-5
T605
- - - - 2/0 S2/0-12R-X
4/0 × 2 × 2 - 4/0 × 4P 4/0 × 4P - S4/0-12R-5
- 300 × 4P - - -
LCA300-12-X
LCAX300-12-6
T720
- - - - 2/0 S2/0-12R-X
- - 4/0 × 4P 4/0 × 4P - S4/0-12R-5
250 × 2 × 2 - - - - S250-12R-5
- 300 × 4P - - -
LCA300-12-X
LCAX300-12-6
*1 For use with PANDUIT Corp. heat-shrinkable tubing HSTT-series or an equivalent UL-recognized heat-shrinkable tubing rated 600 V
minimum.
UL Compliance
Install one of the types of short circuit protection devices to comply with UL 508C. Yaskawa recommends connecting
semiconductor protection fuses. Refer to Three-Phase 200 V Class on page 290, Three-Phase 400 V Class on page
291, and 6-Phase/12-Pulse 400 V Class on page 292 for recommended fuses and alternative short circuit protection
devices.
Semiconductor Protection Fuse
When you use semiconductor fuses as UL listed drive protection, the drives and fuses must be in the same
enclosure.
Where multiple semiconductor fuse ratings are listed for a single drive, Yaskawa recommends a fuse with a large
rated current for applications with repeated loads of approximately 150%. You can use smaller semiconductor
fuses (than what is listed) of the same manufacturer and series. Please note that this can decrease the life of the
fuses.
Non-Semiconductor Fuse
Maximum CC, J, T, RK1 or RK5 fuse rating is 175% of the Normal-Duty drive full load output amp (FLA)
rating.
When you use class CC, J, or T fuses as UL listed drive protection, models 4371 and larger have the same
minimum enclosure volume requirements as MCCBs.
Install Class RK1 or RK5 fuses into a ventilated enclosure with a minimum enclosure volume shown in Table
5.20, Table 5.21, and Table 5.22.
Molded-Case Circuit Breaker (MCCB)
Maximum MCCB rating is 200% of the Normal-Duty drive full load output amp (FLA) rating.
When you use MCCBs, install the drive into a ventilated enclosure with a minimum enclosure volume shown in
Table 5.20, Table 5.21, and Table 5.22.
Note:
Yaskawa recommends current limiting MCCBs.
Short Circuit Current Rating (SCCR)
The maximum SCCR provided by drive and fuse, or drive and MCCB combinations in this document, is 100,000
RMS symmetrical amps.
240 V Cass drives: Use the protection specified in this document to prepare the drive for use on a circuit that
supplies not more than 100,000 RMS and not more than 240 Vac when there is a short circuit in the power supply.
480 V Class drives: Use the protection specified in this document to prepare the drive for use on a circuit that
supplies not more than 100,000 RMS and not more than 480 Vac when there is a short circuit in the power supply.