5.3 UL Standards
290 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Three-Phase 200 V Class
Table 5.20 Required Short Circuit Protection
Drive Model
Drive Mounted without
Supplemental Enclosure
(Using UL Type 1 Kit)
Drive Mounted in Supplemental Enclosure
Any Size Protected Enclosure
(Ventilated/Non-Ventilated)
Restricted Size Protected Enclosure
(Ventilated Only)
Semiconductor
Fuse
Manufacturer:
EATON/
Bussmann
(Permitted Only
in UL Type 1
Kit)
Class CC, J, or
T Fuse
Maximum
Amps
(A)
(Permitted in
Same or
Separate
Enclosure)
Semiconductor
Fuse
Manufacturer:
EATON/
Bussmann
(Drive and
Fuses in Same
Enclosure
Only)
Class CC, J, or
T Fuse
Maximum
Amps
(A)
(Permitted in
Same or
Separate
Enclosure)
These Devices Permitted in Same or Separate Enclosure
Class CC, J, or
T Fuse
Maximum
Amps
(A)
MCCB
Maximum
Amps
(A)
Class RK1 or
RK5 Fuse
Maximum
Amps
(A)
Minimum
Enclosure
Volume
(in
3
)
2004 N/A
*1
7 FWH-45B 7
*2
15 7 4195
2006 N/A
*1
10 FWH-45B 10
*2
15 10 4195
2008 N/A
*1
12 FWH-45B 12
*2
15 12 4195
2010 N/A
*1
15 FWH-45B 15
*2
15 15 4195
2012 N/A
*1
20
FWH-50B, FWH-
80B
20
*2
20 20 4195
2018 N/A
*1
30
FWH-80B, FWH-
100B
30
*2
35 30 4195
2021 N/A
*1
35
FWH-80B, FWH-
100B
35
*2
40 35 4195
2030 N/A
*1
50
FWH-100B,
FWH-125B
50
*2
60 50 4195
2042 N/A
*1
70 FWH-150B 70
*2
80 70 4195
2056 N/A
*1
90 FWH-200B 90
*2
110 90 4195
2070 N/A
*1
110
FWH-200B,
FWH-225A
110
*2
125 110 4195
2082 N/A
*1
125
FWH-225A,
FWH-250A
125
*2
150 125 4195
2110 N/A
*1
175
FWH-225A,
FWH-250A
175
*2
200 175 10121
2138 N/A
*1
225
FWH-275A,
FWH-300A
225
*2
250 225 10121
2169 N/A
*1
250
FWH-275A,
FWH-350A
250
*2
300 250 10121
2211 N/A
*1
350
FWH-325A,
FWH-450A
350
*2
400 350 10121
2257 N/A
*1
400 FWH-600A 400
*2
500 400 14657
2313 N/A
*1
500
FWH-700A,
FWH-800A
500
*2
600 500 14657
2360 N/A
*1
600
FWH-800A,
FWH-1000B
600
*2
700 600 52800
2415 N/A
*1
700 FWH-1000B 700
*2
800 n/a 52800
*1 The UL Type 1 kit does not support internal fuses for this drive model.
*2 Enclosure volume is not restricted. Refer to the values in the “Any Size Protected Enclosure (Ventilated/Non-Ventilated)” column for
acceptable fuses.