Parameter List
11
11.10 H: Terminal Functions
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 591
Setting Value Function Description Ref.
7D Short Circuit Braking (N.
C.)
Sets operation of Short Circuit Braking (N.C.).
ON : Normal operation
OFF : Short Circuit Braking is enabled.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
903
7E Reverse Rotation
Identifier
Sets the rotation direction of the motor when in Simple Closed Loop V/f Control method and F1-21, F1-37 = 0
[Encoder Option Function Selection = A pulse detection], or when in Closed Loop V/f Control method.
ON : Reverse run
OFF : Forward run
904
90 DWEZ Digital Input 1
Sets the DriveWorksEZ digital input 1. Refer to the DriveWorksEZ online manual for more information.
904
91 DWEZ Digital Input 2
Sets the DriveWorksEZ digital input 2. Refer to the DriveWorksEZ online manual for more information.
904
92 DWEZ Digital Input 3
Sets the DriveWorksEZ digital input 3. Refer to the DriveWorksEZ online manual for more information.
904
93 DWEZ Digital Input 4
Sets the DriveWorksEZ digital input 4. Refer to the DriveWorksEZ online manual for more information.
904
94 DWEZ Digital Input 5
Sets the DriveWorksEZ digital input 5. Refer to the DriveWorksEZ online manual for more information.
904
95 DWEZ Digital Input 6
Sets the DriveWorksEZ digital input 6. Refer to the DriveWorksEZ online manual for more information.
904
96 DWEZ Digital Input 7
Sets the DriveWorksEZ digital input 7. Refer to the DriveWorksEZ online manual for more information.
904
97 DWEZ Digital Input 8
Sets the DriveWorksEZ digital input 8. Refer to the DriveWorksEZ online manual for more information.
904
9F DWEZ Disable
Sets operation of the DriveWorksEZ program saved in the drive.
ON : Disabled
OFF : Enabled
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Enabled/Disabled wDigital Input] to use this function.
904
101 !LOCAL/REMOTE
Selection
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
ON : REMOTE
OFF : LOCAL
904
102 !External Reference 1/2
Selection
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
ON : b1-01 = [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
OFF : b1-15 = [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
904
103 !Multi-Step Speed
Reference 1
Uses a combination of multi-step speed references 1, 2 and 3 (N.C.) to set d1-01 to d1-08 [Multi-Step Speed
Reference].
904
104 !Multi-Step Speed
Reference 2
Uses a combination of multi-step speed references 1, 2 and 3 (N.C.) to set d1-01 to d1-08 [Multi-Step Speed
Reference].
904
105 !Multi-Step Speed
Reference 3
Uses a combination of multi-step speed references 1, 2 and 3 (N.C.) to set d1-01 to d1-08 [Multi-Step Speed
Reference].
904
106 !Jog Reference Selection
Sets the drive to use the JOG Frequency Reference (JOG command) set in d1-17 [Jog Reference]. The JOG Frequency
Reference (JOG command) overrides the d1-01 to d1-16 [References 1 to 16].
904
107 !Accel/Decel Time
Selection 1
Sets the drive to use C1-01, C1-02 [Acceleration/Deceleration Time 1] or C1-03, C1-04 [Acceleration/Deceleration
Time 2].
904
10A !Accel/Decel Ramp Hold
Momentarily pauses motor acceleration and deceleration when the terminal deactivates, retains the output frequency
that was stored in the drive at the time of the pause, and restarts motor operation.
904