11.21 Defaults by Drive Model and Duty Rating ND/HD
676 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
No.
*1
Name Unit Default
- Drive Model - 2042 2056 2070 2082
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 006B 006D 006E 006F
E2-11
(E4-11)
Motor Rated
Power
kW 7.5 11 11 15 15 18.5 18.5 22
E5-01
PM Motor
Code Selection
- 120B 120B 120D 120D 120E 120E 120F 120F
L2-02
Power Loss
Ride Through
Time
s 1 1 2 2 2 2 2 2
L2-03
Minimum
Baseblock
Time
s 0.8 0.9 0.9 1 1 1 1 1
L2-04
Powerloss V/f
Recovery
Ramp Time
s 0.3 0.3 0.3 0.6 0.6 0.6 0.6 0.6
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 190 190 190 190 190 190 190 190
L3-24
Motor Accel
Time @ Rated
Torque
s 0.175 0.265 0.265 0.244 0.244 0.317 0.317 0.355
L8-02
Overheat
Alarm Level
°C 110 110 115 115 120 120 133 130
L8-09
Output Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 1 1 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 10 10
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor Inertia
Acceleration
Time
s 0.175 0.265 0.265 0.244 0.244 0.317 0.317 0.355
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 2110 2138 2169 2211
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 0070 0072 0073 0074
E2-11
(E4-11)
Motor Rated
Power
kW 22 30 30 37 37 45 45 55
b3-04
V/f Gain
during Speed
Search
% 100 80 80 80 80 80 80 80
b3-06
Speed
Estimation
Current Level
1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5

Table of Contents