6 Utility Functions (Fn)
6-12
6.6 Initializing Parameter Settings (Fn005)
This function is used when returning to the factory settings after changing parameter settings.
Note: Any value adjusted with Fn00C, Fn00D, Fn00E, and Fn00F cannot be initialized by Fn005.
(1) Preparation
The following conditions must be met to initialize the parameter values.
The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
The servomotor power must be OFF.
(2) Operating Procedure
Use the following procedure.
• Be sure to initialize the parameter settings while the servomotor power is OFF.
• After initialization, turn OFF the power supply and then turn ON again to validate the
settings.
• The parameters of the option module will not be initialized. For information on how to
initialize the parameters of the option module, refer to the manual of the connected
option module.
Step Display after Operation Keys Operation
1
Press the Key to view the main menu for the
utility function.
Use the or Key to move through the list and
select Fn005.
2
Press the Key. The display changes to the Fn005
execution display.
3
Press the Key to initialize parameters.
During initialization, "Parameter Init" is flashing in
the display.
After the initialization is completed, "Parameter Init"
stops flashing and the status display changes as fol-
lows: "BB" to "DONE" to "BB."
Note: Press the Key not to initialize parameters.
The display returns to the main menu of the
utility function.
4 To enable the change in the setting, turn the power OFF and ON again.
BB FUNCTION
Fn004:Program JOG
Fn005:Prm Init
Fn006:AlmHist Clr
Fn008:Mturn Clr
BB
Parameter lnit
Start : [DATA]
Return: [SET]
BB
Parameter lnit
Start : [DATA]
Return: [SET]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA SGDV series and is the answer not in the manual?

YASKAWA SGDV series Specifications

General IconGeneral
SeriesSGDV
CommunicationMECHATROLINK-II, MECHATROLINK-III, EtherCAT
Control ModesPosition, Speed, Torque
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Encoder error
Ambient Temperature0°C to 55°C
Cooling MethodNatural cooling or forced air cooling
Voltage200V, 400V
WeightVaries depending on model (e.g., 0.6 kg to 10 kg)

Related product manuals