6.7 Clearing Alarm History (Fn006)
6-13
6.7 Clearing Alarm History (Fn006)
The clear alarm history function deletes all of the alarm history recorded in the SERVOPACK.
Note: The alarm history is not deleted when the alarm reset is executed or the main circuit power supply of the SERVO-
PACK is turned OFF.
(1) Preparation
The follow conditions must be met to clear the alarm history.
The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
(2) Operating Procedure
Use the following procedure.
Step Display after Operation Keys Operation
1
Press the Key to view the main menu for the
utility function.
Use the or Key to move through the list and
select Fn006.
2
Press the Key. The display changes to the Fn006
execution display.
3
Press the Key to clear the alarm history.
While clearing the data, "DONE" is displayed in the
status display. After the data has been successfully
cleared, "BB" is displayed.
Note: Press the Key not to clear the alarm his-
tory. The display returns to the main menu of
the utility function.
BB FUNCTION
Fn005:Prm Init
Fn006:AlmHist Clr
Fn008:Mturn Clr
Fn009:Ref Adj
BB
Alarm History
Data Clear
Start : [DATA]
Return: [SET]
BB
Alarm History
Data Clear
Start : [DATA]
Return: [SET]