Connecting the power cables
Connection diagram
PE
PE
L1 L2
R-
L3
R+
UDC+
U1
M
W1
3
T1/U T2/V T3/W
V1
(PE) (PE) L1 L2 L3
PE
1
2
3
4
6
4
5
Two protective earth (ground) conductors. Drive safety standard IEC/EN/UL 61800-
5-1 requires two PE conductors if the cross-sectional area of the PE conductor is less
than 10 mm
2
Cu or 16 mm
2
Al. For example, you can use the cable shield in addition to
the fourth conductor.
1
Use a separate grounding cable or a cable with a separate PE conductor for the line
side if the conductivity of the fourth conductor or shield does not meet the requirements
for the PE conductor.
2
Use a separate grounding cable for the motor side if the conductivity of the shield is
not sufficient, or if there is no symmetrically constructed PE conductor in the cable.
3
360-degree grounding of the cable shield is required for the motor cable and brake
resistor cable (if used). It is also recommended for the input power cable.
4
If necessary, install an external filter (d
u
/d
t
, common mode, or sine filter). Filters are
available from ABB.
5
For IP66 (UL Type 4X) drive with optional disconnect, wire to terminals 2T1, 4T2 and
6T3. External disconnect is not needed but external fuses are still required.
6
Electrical installation Global (IEC) 139