Nominal output current (
I
2
) for the minimum switching
frequencies at 40 °C (+104 °F)
Nominal
output
ACS580-
01-…
Frame
size
16 kHz12 kHz8 kHz4 kHz2 kHz1 kHz
I
2
AAAAAAA
3-phase
U
1
= 500…600 V,
P
n
at
U
n
= 575 V, 60 Hz
1.11.51.92.72.72.72.702A7-6R2
1.62.12.83.93.93.93.903A9-6R2
2.43.34.46.16.16.16.106A1-6R2
3.64.96.59.09.09.09.009A0-6R2
4.45.97.911.011.011.011.0011A-6R2
6.89.212.217.017.017.017.0017A-6R2
7.511.015.422.022.022.022.0022A-6R3
9.213.518.927.027.027.027.0027A-6R3
10.916.022.432.032.032.032.0032A-6R3
14.820.928.741.041.041.041.0041A-6R5
18.726.536.452525252052A-6R5
22.331.643.462626262062A-6R5
27.739.35477777777077A-6R5
N/A49.56599999999099A-6R7
N/A6383125125125125125A-6R7
N/A7295144144144144144A-6R8
N/A96127192192192192192A-6R9
N/A121160201242242242242A-6R9
N/A136179201271271271271A-6R9
Output frequency derating
Output frequency derating applies for ratings up to ACS580-01-106A-4 (R5). Inverter
output current is limited by the following factor k below 5 Hz absolute inverter
output frequency f_abs.
k = 2/3 + 1/3 · (f_abs / 5 Hz)
Fuses (IEC)
gG as well as uR or aR fuses for protection against short-circuit in the input power
cable or drive are listed below. Either fuse type can be used for frames R1…R9 if
290 Technical data