ABB ACS580 Series - Surrounding Air Temperature Derating, IP55 (UL Type 12)

ABB ACS580 Series
468 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-099A-6, -125A-6, -144A-6: In the temperature range +40…45 °C (+104…113 °F), the
rated output current is not derated at all. In the temperature range +45…50 °C
(+113…122 °F), the rated output current is derated by 1% for every added 1 °C
(1.8 °F). The output current can be calculated by multiplying the current given in
the rating table by the derating factor (k):
0.90
k
0.80
0.75
0.85
0.95
T
+40 °C
+104 °F
+50 °C
+122 °F
+45 °C
+113 °F
1.00
0.95
-15 °C
+5 °F
Surrounding air temperature derating, IP55 (UL Type 12)
IP55 (UL Type 12) drive types, other than the exceptions below
In the temperature range +40…50 °C (+104…122 °F), the rated output current is
derated by 1% for every added 1 °C (1.8 °F). The output current can be calculated
by multiplying the current given in the rating table by the derating factor (k):
T
1.00
0.90
+40 °C
+104 °F
+50 °C
+122 °F
k
0.80
-15 °C
+5°F
0.85
0.95
IP55 (UL Type 12) drive type -077A-4, -078A-4, -260A-4, -293A-4; -075A-2 (R4), -273A-2,
-276A-2; -099A-6, -125A-6, -144A-6
-077A-4 and -078A-4; -075A-2 (R4): In the temperature range +40…45 °C
(+104…113 °F), the rated output current is derated by 1% for every added 1 °C
(1.8 °F). In the temperature range +45…50 °C (+113…122 °F), the rated output
current is derated by 2.5% for every added 1 °C (1.8 °F). The output current can be
280 Technical data