UL (NEC)
Control cable entries, wire sizes and tightening torques (T) are given below.
Control cable entries and terminal sizesCable entriesFrame
size
DI, AI/O, AGND, RO, STO
terminals
+24V, DCOM, DGND, EXT.
24V terminals
Max cable
size
Holes
T
Wire size
T
Wire size
lbf·ftAWGlbf·ftAWGinpcs
0.426…160.424…140.673R1
0.426…160.424…140.673R2
0.426…160.424…140.673R3
0.426…160.424…140.674R4, R4
v2
0.426…160.424…140.673R5
0.426…160.426…140.674R6
0.426…160.426…140.674R7
0.426…160.426…140.674R8
0.426…140.426…140.674R9
Electrical power network specification
• ACS580-01-xxxx-2 drives: Input voltage range 3~
208…240 V AC +10%…. -15%.
IEC: This is indicated in the type designation label as
typical input voltage levels 3~ 230 V AC.
North America: This is indicated in the type designation
label as typical input voltage levels 1~ 208/230 V AC and
3~ 208/230 V AC.
• ACS580-01-xxxx-4 drives: Input voltage range 3~
380…480 V AC +10%…-15%.
This is indicated in the type designation label as typical
input voltage levels 3~ 400/480 V AC.
• ACS580-01-xxxx-6 drives: Input voltage range 3~
525…600 V AC +10%…-15%.
This is indicated in the type designation label as typical
input voltage level 3~ 600 V AC.
Voltage (
U
1
)
342 Technical data