Loading...
it operates rapidly enough. The operating time depends on the supply network
impedance and the cross-sectional area and length of the supply cable.
Note 1: See also Implementing short-circuit and thermal overload
protection (page 117).
Note 2: Fuses with higher current rating than the recommended ones must not
be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings and
the melting curve of the fuse does not exceed the melting curve of the fuse
mentioned in the table.
gG fuses
Check on the fuse time-current curve to ensure the operating time of the fuse is
below 0.5 seconds. Obey the local regulations.
gG (IEC 60269)Input
current
Min.
short-
circuit
current
1)
ACS580-
01-…
IEC
60269
size
ABB typeVoltage
rating
I
2
tNominal
current
VA
2
sAAA
3-phase
U
n
= 230 V
000OFAF000H255002500254.720004A7-2
000OFAF000H255002500256.720006A7-2
000OFAF000H255002500257.620007A6-2
000OFAF000H2550025002512.0200012A-2
000OFAF000H2550025002516.9200018A-2
000OFAF000H4050077004024.5320025A-2
000OFAF000H4050077004031.2320032A-2
000OFAF000H63500201006346.7500047A-2
000OFAF000H63500201006360500060A-2
00OFAF00H125500103000125891300089A-2
00OFAF00H125500103000125911300091A-2
00OFAF00H1255001030001251151300115A-2
0OFAF0H2005003000002001441700144A-2
0OFAF0H2505006000002501712300171A-2
1OFAF1H3155007100003152133300213A-2
-----273-248A-2