Installing the drive vertically, frames R6…R9
Select fasteners and their application to meet local requirements appropriate to
wall surface materials, drive weight and application.
1. Mark the hole locations for the six mounting holes using the mounting template
included in the package. Do not leave the mounting template under the drive.
The drive dimensions and hole locations are also shown in the drawings in
chapter Dimension drawings (page 363).
Note: You can use only two bolts instead of four to attach the lower part of
the drive.
R9R8R7R6
inmminmminmminmm
c
a
d
e
b
1
× 4
28.371827.670124.562322.5571a
25.965825.965823.058320.9531b
13.634510.32639.72458.4213c
11.830011.830011.830011.8300d
7.92006.191556.11556.1155e
lbkglbkglbkglbkg
IP21,
UL Type 1
213.997152.269119.15493.542.4
lbkglbkglbkglbkg
IP55,
UL Type 12
227.1103169.877123.55694.843
2. Drill the mounting holes.
3. Insert fixing anchors or plugs into the holes and start the bolts into the anchors
or plugs.
4. Position the drive onto the bolts on the wall. Lift the drive with a lifting device
as it is heavy.
5. Tighten the top two bolts in the wall securely.