SettingParameter
Reverse15.07 RO4 source
1 s15.08 RO4 ON delay
1 s15.09 RO4 OFF delay
Parameter setting example for digital output
This example shows how to make digital output DO1 of the extension module
indicate the reverse direction of rotation of the motor with a one-second delay.
SettingParameter
Digital output15.22 DO1 configuration
Reverse15.23 DO1 source
1 s15.24 DO1 ON delay
1 s15.25 DO1 OFF delay
Parameter setting example for frequency output
This example shows how to make digital output DO1 of the extension module
indicate the motor speed 0…1500 rpm with a frequency range of 0…10000 Hz.
SettingParameter
Frequency output15.22 DO1 configuration
01.01 Motor speed used15.33 Freq out 1 source
015.34 Freq out 1 src min
1500.0015.35 Freq out 1 src max
0 Hz15.36 Freq out 1 at src min
10000 Hz15.37 Freq out 1 at src max
Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
LEDs
The extension module has one diagnostic LED.
Optional I/O extension and adapter modules 451