Start-up
Setting the parameters
1. Power up the drive.
2. Verify that the diagnostic LED is on.
Parameter setting example for AI1
This example shows how to set the control unit parameters for a bipolar speed
reference ranging from -50 Hz to 50 Hz, with detection of a wire break between
the adapter module and the control unit of the drive.
DefaultSettingParameter
4.000 mA or 0.000 V0.5 V12.17 AI1 min
20.000 mA or 10.000 V9.5 V12.18 AI1 max
0.000-5012.19 AI1 scaled at AI1 min
505012.20 AI1 scaled at AI1 max
DisabledLow32.05 Supervision 1 function
No actionFault32.06 Supervision 1 action
FrequencyAI132.07 Supervision 1 signal
0.000.432.09 Supervision 1 low