If the warning A7AB Extension I/O configuration failure is shown,
make sure that the value of parameter 15.02 is CMOD-02.
set the parameter 15.01 value to CMOD-02.
You can now see the parameters of the extension module in parameter group
15 I/O extension module.
Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
LEDs
The extension module has one diagnostic LED.
DescriptionColor
The extension module is powered up.Green
Technical data
Into option slot 2 on the drive control unitInstallation
IP20 / UL Type 1Degree of protection
See the drive technical data.Ambient conditions
CardboardPackage
Motor thermistor connection (60…61)
1.5 mm
2
Maximum wire size
DIN 44081 and DIN 44082Supported standards
3.6 kohm ±10%Triggering threshold
1.6 kohm ±10%Recovery threshold
5.0 VPTC terminal voltage
< 1 mAPTC terminal current
< 50 ohm ±10%Short-circuit detec-
tion
The PTC input is reinforced/double insulated. If the motor part of the PTC sensor and wiring
are reinforced/double insulated, voltages on the PTC wiring are within SELV limits.
If the motor PTC circuit is not reinforced/double insulated (ie, it is basic insulated), it is
mandatory to use reinforced/double insulated wiring between the motor PTC and CMOD-
02 PTC terminal.
Relay output (62…63)
1.5 mm
2
Maximum wire size
Optional I/O extension and adapter modules 457