Circuit breakers (UL)
These drives are suitable for use on a circuit capable of delivering not more than
65 kA symmetrical amperes (rms) at 240 / 480 / 600 V maximum (100 kA
symmetrical amperes (rms) for IP66 (UL Type 4X) drives with disconnect and fuse
option at 240 / 480 / 600 V maximum), when protected by appropriate circuit
breakers in the tables below. Additional fuse protection is not required by UL when
using circuit breakers herein. Circuit breakers are not required to be in the same
enclosure as the drive.
Notes below the tables must be followed when using these breakers.
ABB circuit breakerDrive
volume
Enclosure
minimum
volume
CB
voltage
CB
maximum
current
Input
current
Frame
size
ACS580-
01-…
65 kA @ 240 Vin
3
in
3
VAA
3-phase
U
1
= 200…240 V,
P
n
at
U
n
= 208/230 V, 60 Hz
XT2Nαβ025#********561¤240254.6R104A6-2
XT2Nαβ025#********561¤240256.6R106A6-2
XT2Nαβ025#********561¤240257.5R107A5-2
XT2Nαβ025#********561¤2402510.6R110A6-2
XT2Nαβ025#********561¤2402516.7R1017A-2
XT2Nαβ040#********737¤2404024.2R2024A-2
XT2Nαβ040#********737¤2404030.8R2031A-2
XT2Nαβ100#********1390¤24010046.2R3046A-2
XT2Nαβ100#********1390¤24010059.4R3059A-2
XT2Nαβ100#********2027¤24010074.8R4075A-2
XT4Nαβ150#********2181¤24015088.0R5088A-2
XT4Nαβ150#********2181¤240150114R5114A-2
XT4Nαβ200#********2880¤240200143R6143A-2
XT5Nαβ30A#********3369¤240300169R7169A-2
XT5Nαβ30A#********3369¤240300211R7211A-2
XT5Nαβ40A#********3858¤240400273R8273A-2
¤ Enclosure minimum volume is not applicable
See notes 1-11 below